ELECTRICAL CIRCUIT BREAKERS
- Description: The Contractor shall comply with the provisions of Section 15001: General M&E Requirements. Each low voltage Circuit Breaker (CB) shall be suitable for controlling loads as indicated and shall confirm to IEC 60947-2 Utilisation Category B or other approved equivalent standard for 415V 3-phase 50Hz 4-wire operation. All low voltage circuit breakers shall be housed in MCCs/Control Boards/Cubicles, which comply with the requirements of Section 16020: Factory Built Assembly (FBA).
- Standards: Local
- Location: Abu Zabi
- Categories: Fire Protection, Structure, Mechanical, Electrical, Plumbing, Generic
- Sub Categories: Architecture
- Posted: February 3rd, 2022, 11:01 am
- GENERAL
- LOW VOLTAGE ACB
- LOW VOLTAGE MCCB
- MCB
- EARTH LEAKAGE CIRCUIT BREAKERS (ELCB OR RCCB)
- RESIDUAL CURRENT BREAKER WITH OVERCURRENT PROTECTION (RCBO)
- SOURCE TESTS