ELECTRICAL POWER MONITOR (PM)
- Description: The Contractor shall comply with the provisions of Section 15001: General M&E Requirements. The Power Monitor (PM) shall be a true RMS digital instrument, with LCD display, capable of controlling and measurement of highly nonlinear loads accurately and able to detect voltage-based disturbances The LCD unit, complete with integral function keys, shall be minimum IP54 and be mounted locally on the Incomer cubicle door. The PM shall be ‘CE marked’ and confirm to BS EN 61010-1. The PM shall register all measured values and log current and previous measured values for reporting and printing purposes. The PM shall be supplied with software, user manual and associated interconnecting cables. The PM shall be provided with user-friendly software program (fully supported by the latest edition of a Windows®-based operating system) allowing easy access to all features with pull-down menus.
- Standards: Local
- Location: Abu Zabi
- Categories: Fire Protection, Architecture, Structure, Mechanical, Electrical, Plumbing, Generic
- Sub Categories: Architecture
- Posted: February 3rd, 2022, 11:30 am
- GENERAL
- FEATURES
- MEASUREMENTS