ELECTRICAL STARTERS
- Description: The Contractor shall comply with the provisions of Section 15001: General M&E Requirements. Starter components shall form part of a Motor Control Centre (MCC) described under Section 16020: Factory Built Assembly (FBA) and Section 16030: Motor Control Centre (MCC) and as such circuit connections, protection devices and the like shall comply with BS EN 60439-1. b) Starters and their components shall provide Type 2 Co-ordination to BS EN 60947-4-1. They shall be so arranged to provide easy access to all components for maintenance purposes. Starter shall be damp-proof and dust-proof with a minimum Ingress Protection (IP) rating of IP 54. Motor starters shall be rated to carry full load current of its rated duty at its most severe load conditions. All starters shall be selected for Utilisation Category AC3 duty and be capable of at least 15 starts per hour at 100% full load torque. The starting method employed to start the motors shall be as described herein, unless specified otherwise on relevant contract drawings. Standalone Unit Control Panels, where supplied by a manufacturer of Packaged Type Plant, shall confirm to the requirements specified herein. All starters shall be provided with phase failure and phase reversal protection.
- Standards: Local
- Location: Abu Zabi
- Categories: Fire Protection, Architecture, Structure, Mechanical, Electrical, Plumbing, Generic
- Sub Categories: Architecture
- Posted: February 3rd, 2022, 10:47 am
- GENERAL
- DIRECT ON LINE FULL-VOLTAGE MOTOR STARTER
- UP TO 4.0KW INCLUSIVE
- STAR/DELTA (S/D) REDUCED-VOLTAGE MOTOR STARTER
- 5.5KW – 11.0KW INCLUSIVE
- SOFT STARTERS
- 15.0KW AND ABOVE
- CONTACTORS